Fieldbus systemseries MVE |
|
|||||||||||||||||||
The fieldbus system of the MVE series system allows the connection and control of valves and other inputs and outputs using the EtherNet / IP protocol. Up to 23 channels are available in one set for the control of associated valves (MVSY 100 and MVSY 156 series) as well as up to 8 input and output units, with 8 inputs or 8 outputs in each unit. It is therefore easy to connect and control the island with valves and send back to the control system, for example, the states of the end position sensors. The configuration can be modified using a web browser or using a configuration program on a computer. Both the main and I/O units have LEDs that inform the user of the status.
|
DI unit
Specification
Description | Value |
Inpout type | PNP or NPN |
Input connector | 8x M8 (3 pins) |
Number of inputs | 8 (1 input / connector) |
Sensor supplied voltage | 24V DC |
Max. sensor supplied current | 0,25A / connector, 2A / unit |
Rated input current | 9 mA |
ON voltage (NPN input) (between the pin for input terminal and supplied voltage of +24V) |
≥17V |
OFF voltage (PNP input) (between the pin for input terminal and supplied voltage of 0V) |
≤5V |
Features | Short / open - circuit detection |
Power supply voltage | 24V DC class 2, 2A |
Working environment | temperature -10°C to +50°C, humidity 35% to 85% RH |
Isolation | 500V AC, 10MΩ |
Connectors
|
Pin arrangement
Socket | PIN | Signal |
1 | 24V (control and input) | |
2 | 0V (control and input) | |
3 | input |
LED indicator
|