Fieldbus systemseries MVE |
|
|||||||||||||||||||
The fieldbus system of the MVE series system allows the connection and control of valves and other inputs and outputs using the EtherNet / IP protocol. Up to 23 channels are available in one set for the control of associated valves (MVSY 100 and MVSY 156 series) as well as up to 8 input and output units, with 8 inputs or 8 outputs in each unit. It is therefore easy to connect and control the island with valves and send back to the control system, for example, the states of the end position sensors. The configuration can be modified using a web browser or using a configuration program on a computer. Both the main and I/O units have LEDs that inform the user of the status.
|
SI unit
Specification
Description | Value |
Interface protocol | EtherNet/IP |
Communication speed | 10/100 Mbps |
Configuration file | EDS |
Power connector | M12 (5 pins) |
Control & input power supply | 24V DC class 2, 2A |
Output power supply | 24V DC class 2, 2A |
Consumption | 12W |
Polarity of output for valves | PNP (-COM), NPN (+COM) |
Power supply of valves | 24V DC class 2, 2A |
Number of valve outputs | 23 |
Suitable valves | MVSY 100, MVSY 156, 24V DC |
Fail safe of valves | hold, off, setting value |
Protective function for valve | short circuit protrction |
Working environment | temperature -20°C to +50°C, humidity 10% to 90% RH |
Connectors
|
Pin arrangement
Power
Plug, B coded | PIN | Signal |
1 | 24 V (Output) | |
2 | 0 V (Output) | |
3 | 24 V (Control and input) | |
4 | 0 V (Control and input) | |
5 | FE |
Ethernet/IP
Socket, D coded | PIN | Signal |
1 | TX + | |
2 | RX + | |
3 | TX - | |
4 | RX - |